• Brand: ABB
  • Phase: 3 Phase Input- 1 Phase Output
  • Capacity: 10-40 KVA 
  • PRICE:CALL @ 01720-566000
  • Mounting: Rack-Tower Convertible
  •  

Energy savings thanks to 93% efficiency.

 97% efficiency in ECO mode.

Low harmonic distortions (< 5% THDi) and active power factor correction (0.99 input PF) eliminate interference from other equipment in the network.

Paralleling up to 4 units allows for increase of capacity and introduction of redundancy to system to enhance availability.

Integrated manual bypass switch simplifies maintenance and reduces need for external switchgears.

Can operate as frequency converter (50 Hz to/from 60 Hz)

Compact solution that can achieve 5-16 min runtime with internal batteries.

Same model supports different wiring schemes:  three-phase and single-phase input as well as single 

and dual input feed.

GENERAL DATA

10 KVA

20 KVA

Output rated power [W]

9KW

18KW

Output power factor

0.9

Topology

True Online Double Conversion

Parallel Configuration

Up to 4 units

Up to 4 units

Inbuilt batteries

Yes

Yes

INPUT

 

Nominal input voltage

1 Ph + N: 220/230/240 Vac

3 Ph + N: 380/400/415 Vac

Input voltage tolerance

1 Ph: 110-276 Vac

3 Ph: 190-486 Vac

Input current THD

< 5% at 100 % (sinewave)

Frequency range

45 – 55 Hz / 54 – 65 Hz

Power factor

≥ 0.99

OUTPUT

 

Rated output voltage

220/230/240 Vac

Voltage tolerance

± 2 % (static and dynamic)

Voltage distortion

< 2 % linear load, < 5 % non-linear load (IEC / EN62040-3)

Nominal frequency

50 Hz or 60 Hz ±0.1 Hz

Frequency tolerance

45 – 55 Hz/54 – 66 Hz

Crest Factor

3:1

EFFICIENCY

 

AC-AC

Up to 93 %

Up to 93 %

In eco-mode

Up to 97 %

Up to 97 %

ENVIRONMENT

 

Protection rating

IP 20

Storage temperature

-15 – +60°C

Operating temperature

0 – +45°C

Relative humudity

20 – 90 % (non-condensing)

Altitude (above sea level)

1000 m without de-rating

BATTERIES

 

Types

VRLA, vented lead-acid, NiCd

COMMUNICATIONS

 

User interface

LCD display

Communication cards (option)

SNMP, AS400, Relay card

STANDARDS

 

Safety

IEC/EN 62040-1

EMC

IEC/EN 62040-2

Performance

IEC/EN 62040-3

Manufacturing

ISO 9001:2008, ISO 14001:2004